InRow RP Technical Data Manual20
Chilled Water Performance Specifications 10°C (50°F) EWT
Temperature dry
bulb (DB), wet bulb
(WB)
°C (°F)
CW Delta T
°C (°F)
Total Net
Capacity
kW (BTU/hr)
Sensible Net
Capacity
kW (BTU/hr)
Sensible Heat
Ratio
SHR
CW Flow Rate
l/s (GPM)
Total CW
Pressure Drop
kPa (ft H
2
O)*
26.7°C DB, 17.1°C WB (80°F DB, 62.8°F WB)
5.5 (10) 32.6 (111,000) 31.8 (109,000) 0.98 1.5 (23.5) 54 (18.02)
6.6 (12) 29.9 (102,000) 29.2 (100,000) 0.98 1.1 (18.1) 33 (11.1)
7.7 (14) 27.4 (93,000) 26.7 (91,000) 0.98 0.9 (14.3) 21 (6.9)
8.8 (16) 24.9 (85,000) 24.3 (83,000) 0.98 0.7 (11.5) 14 (4.6)
10 (18) 22.6 (77,000) 22.0 (75,000) 0.98 0.6 (9.4) 10 (3.2)
11.1 (20) 20.4 (70,000) 19.9 (68,000) 0.98 0.5 (7.7) 7 (2.3)
29.4°C DB, 18.1°C WB (85°F DB, 64.5°F WB)
5.5 (10) 39.6 (135,000) 38.6 (132,000) 0.98 1.8 (28.0) 76 (25.6)
6.6 (12) 36.6 (125,000) 35.7 (122,000) 0.98 1.4 (21.8) 47 (15.7)
7.7 (14) 33.8 (115,000) 32.9 (112,000) 0.98 1.1 (17.3) 30 (10.2)
8.8 (16) 31.1 (106,000) 30.3 (103,000) 0.98 0.9 (14.0) 20 (6.7)
10 (18) 28.5 (97,000) 27.7 (95,000) 0.98 0.7 (11.5) 14 (4.6)
11.1 (20) 26.0 (89,000) 25.3 (86,000) 0.98 0.6 (9.5) 10 (3.2)
32.2°C DB, 18.9°C WB (90°F DB, 66.1°F WB)
6.6 (12) 43.6 (149,000) 43.2 (147,000) 0.99 1.6 (25.6) 64 (21.5)
7.7 (14) 40.5 (138,000) 40.1 (137,000) 0.99 1.3 (20.5) 42 (13.9)
8.8 (16) 37.6 (128,000) 37.2 (127,000) 0.99 1.1 (16.7) 28 (9.5)
10 (18) 34.7 (119,000) 34.4 (117,000) 0.99 0.9 (13.8) 20 (6.5)
11.1 (20) 32.0 (109,000) 31.7 (108,000) 0.99 0.7 (11.5) 14 (4.6)
35.0°C DB, 19.8°C WB (95°F DB, 67.7°F WB)
6.6 (12) 51.9 (177,000) 51.4 (175,000) 0.99 1.9 (30.1) 88 (29.3)
7.7 (14) 48.5 (166,000) 48.0 (164,000) 0.99 1.5 (24.2) 58 (19.4)
8.8 (16) 45.3 (155,000) 44.8 (153,000) 0.99 1.3 (19.9) 39 (13.2)
10 (18) 42.1 (144,000) 41.7 (142,000) 0.99 1.0 (16.5) 28 (9.2)
11.1 (20) 38.7 (132,000) 38.7 (132,000) 1.00 0.9 (13.7) 19 (6.5)
37.8°C DB, 20.7°C WB (100°F DB, 69.2°F WB)
7.7 (14) 56.7 (194,000) 56.7 (194,000) 1.00 1.8 (28.1) 77 (25.6)
8.8 (16) 53.2 (182,000) 53.2 (182,000) 1.00 1.5 (23.1) 53 (17.6)
10 (18) 49.8 (170,000) 49.8 (170,000) 1.00 1.2 (19.3) 37 (12.5)
40.6°C DB, 21.6°C WB (105°F DB, 70.8°F WB)
8.8 (16) 62.3 (213,000) 62.3 (213,000) 1.00 1.7 (26.9) 70 (23.6)
Note: All values are accurate to +/- 5% and based on full speed with standard filters.
Note: Reduce airflow and cooling capacity specifications by 7% for cooling units run at low input voltage (380 V).
Note: Any CW flow rate of 0.19 l/s - 0.32 l/s (3.0 GPM - 5.0 GPM) may cause an increased error in flow rate and power calculation. A
fluid flow fault may result. Any flow rate under 0.19 l/s (3.0 GPM) may also display as 0 in the flow rate and power calculation.
Note: For sustained operation, a maximimum flow rate of 2.2 l/s (34 GPM) is recommended. This may be exceeded by 25% for peak
conditions.
* To convert feet of water to PSIG, use the following formula: ft H
2
O ÷ 2.307 = PSIG.