4.4

Out of 1 Ratings

Owner's of the APC Water Dispenser INROW RP gave it a score of 4.4 out of 5. Here's how the scores stacked up:
  • Reliability

    5.0 out of 5
  • Durability

    4.0 out of 5
  • Maintenance

    4.0 out of 5
  • Performance

    5.0 out of 5
  • Ease of Use

    4.0 out of 5
of 50
 
InRow RP Technical Data Manual26
Sound Performance Data
Electrical Data
Chilled Water Tested Sound Data
Fan Speed% Airflow m
3
/s
(SCFM)
Sound Power dB at Frequency Hz re: 10
-12
W Lp Sound Pressure dB
re: 20 microPa*
125 250 500 1000 2000 4000 8000 dBA dBA
35 1.13 (2500) 69.5 37.5 63.5 60.0 54.0 47.5 40.0 65.4 54.9
50 1.79 (3800) 84.0 79.0 75.5 69.5 67.5 58.5 53.5 76.9 66.8
70 2.55 (5400) 92.0 87.0 83.5 79.0 74.5 69.5 63.5 85.9 75.0
85 3.04 (6450) 92.0 95.0 89.0 84.5 79.0 74.5 69.0 90.6 80.7
100 3.26 (6900) 90.0 96.5 90.5 85.0 80.5 76.0 70.5 91.7 81.9
*Weighted Sound Pressure dBA in a 232.2 m
3
(8200 ft
3
) room at 6 ft (1.8 m) distance.
Air-cooled Tested Sound Data
Fan Speed% Airflow m
3
/s
(SCFM)
Sound Power dB at Frequency Hz re: 10
-12
W Lp Sound
Pressure dB re: 20
microPa*
125 250 500 1000 2000 4000 8000 dBA** dBA
50 1.27 (2700) 84.5 87.5 78.0 77.5 75.0 66.5 65.5 83.4 72.8
75 1.79 (3800) 92.5 90.0 84.0 81.5 77.5 71.5 68.5 87.6 76.8
100 2.26 (4800) 90.0 98.0 91.0 85.0 81.0 76.5 72.0 92.3 82.8
*Weighted Sound Pressure dBA in a 8200 ft
3
(232.2 m
3
) room at 6 ft (1.8 m) distance.
**Based on compressor operating at full speed.
SKU Voltage MCA MOP LRA RLA FLA Hz Power (kW)
ACRP100 200 - 240 80.1 100 160* 50.0 N/A 50/60 19
ACRP101 460 - 480 39.9 50 139* 23.2 N/A 60 21
ACRP102 380 - 415 N/A N/A 139* 23.2 32* 50/60 20
ACRP500 200 - 240 46.8 50 N/A N/A N/A 50/60 14
ACRP501 460 - 480 24.8 30 N/A N/A N/A 60 14
ACRP502 380 - 415 N/A N/A N/A N/A 24** 50/60 15
Note: Above data is based on maximum operating condition
*Local or national codes may require the installation of an external disconnect. The disconnect must be rated properly for the
equipment.
**Local or national codes may require the installation of external disconnects. Two disconnects would be required and must be rated
properly for the equipment.
MCA - Minimum Circuit Ampacity
MOP - Maximum Overcurrent Protection
LRA - Locked Rotor Amps
RLA - Rated Load Amps
FLA - Full Load Amps