Remote Power-Off Device Installation and Quick Start 21
Configuration and Setup: How to Turn Off the Output of Multiple UPSs
Matrix-UPS
®
in a
cascading
configuration
You can include only one APC Matrix-UPS in a cascading
configuration, and you must place it at the end of the series of
UPSs (UPS n in the example setup).
Connect
multiple RPOs in
parallel setup
(voltage input
switches only)
You can set up a remote voltage input switch by connecting
multiple Remote Power-Off Devices in parallel.
UPS 1
UPS n
Pin 3
Pin 4
Wiring to voltage input remote switch
RJ-11 cable
Keystone jack
Warning
To avoid equipment damage and false RPO
signals, use a parallel configuration only with a
voltage input remote switch. To connect multiple
RPOs to one contact closure switch, see “Cascade
multiple RPOs (serial setup)” on page 20.