0

Out of 0 Ratings

Owner's of the APC Water Dispenser INROW RP gave it a score of 0 out of 5. Here's how the scores stacked up:
  • Reliability

    0 out of 5
  • Durability

    0 out of 5
  • Maintenance

    0 out of 5
  • Performance

    0 out of 5
  • Ease of Use

    0 out of 5
of 50
 
InRow RP Technical Data Manual18
Chilled Water Performance Specifications 7.2°C (45°F) EWT
Temperature dry bulb
(DB), wet bulb (WB)
°C (°F)
CW Delta T
°C (°F)
Total Net
Capacity
kW (BTU/hr)
Sensible Net
Capacity
kW (BTU/hr)
Sensible Heat
Ratio
SHR
CW Flow Rate
l/s (GPM)
Total CW
Pressure Drop
kPa (ft H
2
O)*
26.7°C DB, 17.1°C WB (80°F DB, 62.8°F WB)
5.5 (10) 40.8 (139,000) 39.6 (135,000) 0.97 1.8 (28.8) 81 (27.03)
6.6 (12) 37.9 (130,000) 36.8 (126,000) 0.97 1.4 (22.5) 50 (16.6)
7.7 (14) 35.1 (120,000) 34.1 (116,000) 0.97 1.1 (18.0) 32 (10.9)
8.8 (16) 32.5 (111,000) 31.5 (108,000) 0.97 0.9 (14.6) 22 (7.4)
10 (18) 29.8 (102,000) 28.9 (99,000) 0.97 0.8 (12.0) 15 (5.1)
11.1 (20) 27.3 (93,000) 26.5 (90,000) 0.97 0.6 (10.0) 11 (3.7)
29.4°C DB, 18.1°C WB (85°F DB, 64.5°F WB)
6.6 (12) 45.0 (154,000) 43.7 (149,000) 0.97 1.7 (26.4) 68 (22.6)
7.7 (14) 42.0 (144,000) 40.8 (139,000) 0.97 1.3 (21.2) 44 (14.8)
8.8 (16) 39.1 (134,000) 38.0 (130,000) 0.97 1.1 (17.4) 30 (10.2)
10 (18) 36.3 (124,000) 35.2 (120,000) 0.97 0.9 (14.4) 21 (7.2)
11.1 (20) 33.3 (114,000) 32.6 (111,000) 0.98 0.8 (11.9) 15 (5.1)
32.2°C DB, 18.9°C WB (90°F DB, 66.1°F WB)
6.6 (12) 52.3 (179,000) 51.2 (175,000) 0.98 1.9 (30.4) 89 (29.8)
7.7 (14) 49.2 (168,000) 48.2 (165,000) 0.98 1.5 (24.5) 59 (19.9)
8.8 (16) 46.1 (157,000) 45.2 (154,000) 0.98 1.3 (20.2) 41 (13.6)
10 (18) 42.7 (146,000) 42.3 (144,000) 0.99 1.1 (16.7) 28 (9.5)
11.1 (20) 39.8 (136,000) 39.4 (135,000) 0.99 0.9 (14.1) 20 (6.9)
35.0°C DB, 19.8°C WB (95°F DB, 67.7°F WB)
7.7 (14) 57.2 (195,000) 56.0 (191,000) 0.98 1.8 (28.3) 78 (26.1)
8.8 (16) 53.4 (182,000) 52.9 (181,000) 0.99 1.5 (23.2) 53 (17.8)
10 (18) 50.3 (172,000) 49.8 (170,000) 0.99 1.2 (19.5) 38 (12.7)
11.1 (20) 47.2 (161,000) 46.7 (160,000) 0.99 1.0 (16.5) 28 (9.2)
37.8°C DB, 20.7°C WB (100°F DB, 69.2°F WB)
8.8 (16) 61.6 (210,000) 61.0 (208,000) 0.99 1.7 (26.6) 69 (23.1)
10 (18) 58.3 (199,000) 57.7 (197,000) 0.99 1.4 (22.4) 50 (16.6)
11.1 (20) 55.1 (188,000) 54.5 (186,000) 0.99 1.2 (19.1) 36 (12.2)
40.6°C DB, 21.6°C WB (105°F DB, 70.8°F WB)
8.8 (16) 69.6 (238,000) 69.6 (238,000) 1.00 1.9 (29.9) 86 (28.9)
10 (18) 66.1 (226,000) 66.1 (226,000) 1.00 1.6 (25.3) 63 (21.02)
11.1 (20) 62.7 (214,000) 62.7 (214,000) 1.00 1.4 (21.7) 46 (15.5)
Note: All values are accurate to +/- 5% and based on full speed with standard filters.
Note: Reduce airflow and cooling capacity specifications by 7% for cooling units run at low input voltage (380 V).
Note: Any CW flow rate of 0.19 l/s - 0.32 l/s (3.0 GPM - 5.0 GPM) may cause an increased error in flow rate and power calculation. A
fluid flow fault may result. Any flow rate under 0.19 l/s (3.0 GPM) may also display as 0 in the flow rate and power calculation.
Note: For sustained operation, a maximimum flow rate of 2.2 l/s (34 GPM) is recommended. This may be exceeded by 25% for peak
conditions.
* To convert feet of water to PSIG, use the following formula: ft H
2
O ÷ 2.307 = PSIG.