4.4

Out of 1 Ratings

Owner's of the APC Water Dispenser INROW RP gave it a score of 4.4 out of 5. Here's how the scores stacked up:
  • Reliability

    5.0 out of 5
  • Durability

    4.0 out of 5
  • Maintenance

    4.0 out of 5
  • Performance

    5.0 out of 5
  • Ease of Use

    4.0 out of 5
of 50
 
17InRow RP Technical Data Manual
Performance Specifications
Chilled Water Performance Specifications 5.5°C (42°F) EWT
Temperature dry bulb
(DB), wet bulb (WB)
°C (°F)
CW Delta T
°C (°F)
Total Net
Capacity
kW (BTU/hr)
Sensible Net
Capacity
kW (BTU/hr)
Sensible Heat
Ratio
SHR
CW Flow
Rate
l/s (GPM)
Total CW
Pressure Drop
kPa (ft H
2
O)*
26.7°C DB, 17.1°C WB (80°F DB, 62.8°F WB)
6.6 (12) 44.3 (151,000) 40.7 (139,000) 0.92 1.6 (25.9) 66 (21.95)
7.7 (14) 40.8 (139,000) 37.9 (129,000) 0.93 1.3 (20.6) 42 (14.1)
8.8 (16) 37.8 (129,000) 35.2 (120,000) 0.93 1.1 (16.8) 29 (9.5)
10 (18) 34.6 (118,000) 32.5 (111,000) 0.94 0.9 (13.8) 19 (6.5)
11.1 (20) 31.8 (109,000) 29.9 (102,000) 0.94 0.7 (11.5) 14 (4.6)
29.4°C DB, 18.1°C WB (85°F DB, 64.5°F WB)
6.6 (12) 50.8 (174,000) 47.8 (163,000) 0.94 1.9 (29.5) 84 (28.4)
7.7 (14) 47.7 (163,000) 44.8 (153,000) 0.94 1.5 (23.9) 56 (18.7)
8.8 (16) 44.1 (151,000) 41.9 (143,000) 0.95 1.2 (19.4) 38 (12.5)
10 (18) 41.2 (141,000) 39.1 (134,000) 0.95 1.0 (16.2) 26 (8.8)
11.1 (20) 37.8 (129,000) 36.3 (124,000) 0.96 0.8 (13.5) 19 (6.2)
32.2°C DB, 18.9°C WB (90°F DB, 66.1°F WB)
7.7 (14) 54.5 (186,000) 52.3 (179,000) 0.96 1.7 (27.1) 71 (23.8)
8.8 (16) 51.4 (175,000) 49.3 (168,000) 0.96 1.4 (22.4) 49 (16.6)
10 (18) 47.8 (163,000) 46.3 (158,000) 0.97 1.2 (18.6) 35 (11.6)
11.1 (20) 44.8 (153,000) 43.4 (148,000) 0.97 1.0 (15.7) 25 (8.32)
35.0°C DB, 19.8°C WB (95°F DB, 67.7°F WB)
7.7 (14) 62.0 (212,000) 60.2 (205,000) 0.97 1.9 (30.6) 90 (30.3)
8.8 (16) 58.8 (201,000) 57.0 (195,000) 0.97 1.6 (25.4) 63 (21.3)
10 (18) 55.6 (190,000) 53.9 (184,000) 0.97 1.4 (21.4) 45 (15.2)
11.1 (20) 52.4 (179,000) 50.9 (174,000) 0.97 1.2 (18.3) 33 (11.1)
37.8°C DB, 20.7°C WB (100°F DB, 69.2°F WB)
8.8 (16) 66.4 (227,000) 65.0 (222,000) 0.98 1.8 (28.6) 79 (26.6)
10 (18) 63.1 (215,000) 61.8 (211,000) 0.98 1.5 (24.2) 57 (19.2)
11.1 (20) 59.8 (204,000) 58.7 (200,000) 0.98 1.3 (20.7) 42 (14.3)
40.6°C DB, 21.6°C WB (105°F DB, 70.8°F WB)
10 (18) 71.4 (244,000) 70.0 (239,000) 0.98 1.7 (27.3) 72 (24.3)
11.1 (20) 68.1 (233,000) 66.7 (228,000) 0.98 1.5 (23.4) 54 (18.02)
Note: All values are accurate to +/- 5% and based on full speed with standard filters.
Note: Reduce airflow and cooling capacity specifications by 7% for cooling units run at low input voltage (380 V).
Note: Any CW flow rate of 0.19 l/s - 0.32 l/s (3.0 GPM - 5.0 GPM) may cause an increased error in flow rate and power calculation. A
fluid flow fault may result. Any flow rate under 0.19 l/s (3.0 GPM) may also display as 0 in the flow rate and power calculation.
Note: For sustained operation, a maximimum flow rate of 2.2 l/s (34 GPM) is recommended. This may be exceeded by 25% for peak
conditions.
* To convert feet of water to PSIG, use the following formula: ft H
2
O ÷ 2.307 = PSIG.